lemonergy/ data

Rechargeable cell · Lead-acid · Flooded · PbO2/Pb · prismatic

Exide Classic 6 OPzS 300 LA

310 Ah lead-acid (Flooded) prismatic cell from Exide. Every value below is read from the datasheet and keeps the conditions it was stated at; what the source does not state is marked as not stated.

Capacity
310 Ah0.1 C · 20 °C · to 1.8 V
Nominal voltage
2 V
Energy
620 Whcalculated by Lemonergy from stated values: capacity × voltage
Mass
23.3 kg
Specific energy
27 Wh/kgcalculated by Lemonergy from stated values
Energy density
51 Wh/Lcalculated by Lemonergy from stated values
Dimensions
147 × 208 × 395 mm
Continuous discharge
Not stated
Cycle life
Not stated
Internal resistance
Not stated
Operating temperature
Not stated

Compare in the finderSource documentRecord as JSON (API)Report a correction

Not offered in Lemonergy Design, which takes lithium-ion and sodium-ion cells only.

Specifications

8 quantities stated by the datasheet, grouped as in the finder. Conditions are the rate, temperature and limits each value was stated at.

Current and power

QuantityValueConditionsFrom the source
Short-circuit current3,250 Anone recordedNot stated: temperature6 OPzS 300 LA | NVZS020300WC0FB | 2 | 310 | 147 | 157 | 208 | 395 | 23.3 | 6.90 | 0.63 | 3250 | F-M8page 2, Page 2, Technical characteristics and data, row 6 OPzS 300 LA, column Short circuit current A

Electrical

QuantityValueConditionsFrom the source
Nominal voltage2 Vnominal value6 OPzS 300 LA | NVZS020300WC0FB | 2 | 310 | 147 | 157 | 208 | 395 | 23.3 | 6.90 | 0.63 | 3250 | F-M8page 2, Page 2, Technical characteristics and data, row 6 OPzS 300 LA, column Nom. voltage
Capacity310 Ah0.1 C · 20 °C · to 1.8 V · nominal value6 OPzS 300 LA | NVZS020300WC0FB | 2 | 310 | 147 | 157 | 208 | 395 | 23.3 | 6.90 | 0.63 | 3250 | F-M8page 2, Page 2, Technical characteristics and data, row 6 OPzS 300 LA, column Nominal capacity C10 1.80 Vpc 20 °C

Lifetime

QuantityValueConditionsFrom the source
Calendar life20 year20 °C · design valueNot stated: state of charge• 20 years design life at 20 °C ambient temperature (until 80% nominal C10)page 1, Page 1, Technical features

Physical

QuantityValueConditionsFrom the source
Mass23.3 kgtypical value6 OPzS 300 LA | NVZS020300WC0FB | 2 | 310 | 147 | 157 | 208 | 395 | 23.3 | 6.90 | 0.63 | 3250 | F-M8page 2, Page 2, Technical characteristics and data, row 6 OPzS 300 LA, column Weight incl. acid** approx. kg
Height395 mmmaximum value6 OPzS 300 LA | NVZS020300WC0FB | 2 | 310 | 147 | 157 | 208 | 395 | 23.3 | 6.90 | 0.63 | 3250 | F-M8page 2, Page 2, Technical characteristics and data, row 6 OPzS 300 LA, column Height* (h) max. mm
Length147 mmmaximum value6 OPzS 300 LA | NVZS020300WC0FB | 2 | 310 | 147 | 157 | 208 | 395 | 23.3 | 6.90 | 0.63 | 3250 | F-M8page 2, Page 2, Technical characteristics and data, row 6 OPzS 300 LA, column Length (l) max. mm
Length157 mmmaximum value6 OPzS 300 LA | NVZS020300WC0FB | 2 | 310 | 147 | 157 | 208 | 395 | 23.3 | 6.90 | 0.63 | 3250 | F-M8page 2, Page 2, Technical characteristics and data, row 6 OPzS 300 LA, column Installed length (L) max. mm
Width208 mmmaximum value6 OPzS 300 LA | NVZS020300WC0FB | 2 | 310 | 147 | 157 | 208 | 395 | 23.3 | 6.90 | 0.63 | 3250 | F-M8page 2, Page 2, Technical characteristics and data, row 6 OPzS 300 LA, column Width (w) max. mm

Chemistry

Classified as
Lead-acid · Flooded · PbO2/Pb
Designation
Lead-acid flooded
Electrolyte
Diluted sulphuric acid, dN = 1.24 kg/l

Source and dates

Document
Classic OPzS Technical data sheet
Kind
datasheet
SHA-256
4debaadb1419d7b9832aff17ad308430ab4287a473ea717b86e64a8869eed3af
Note
Facts only; source body is not redistributed. 15-page Exide technical data sheet (1,056,049 bytes; PDF created 2024-03-25; no printed date or revision). Reached from https://www.exidegroup.com/eu/en/document/classic-opzs-datasheet. Main table on page 2: nominal capacity C10 to 1.80 Vpc at 20 °C; dimensions are maxima; height includes the installed connector and 'can differ depending on the used vent(s)'; weight includes acid and 'may differ by ±5%'. The separate acid weight is not recorded. Flooded is read from the sheet's liquid electrolyte ('diluted sulphuric acid') and its 'W (wet)' part-number code; the word 'flooded' is not printed. Internal resistance is printed without its method and is not recorded. The constant-current and constant-power discharge tables (pages 4-15) are not transcribed; they are kept for the later lead-acid design work.
Source document date
Not recorded (evidence)
Source revision
Not recorded
Specification source retrieved
2026-10-29 (day precision) (evidence)
Product lifecycle checked
Not recorded
Product release
Not researched
Date context
Source retrieval and document revision do not establish product release or current availability.
Record
contrib/cells/exide/classic-6-opzs-300-la.yaml

How to cite

Exide. “Classic OPzS Technical data sheet”, datasheet. https://www.exidegroup.com/eu/sites/default/files/2024-03/Classic_OPzS_technicaldata.pdf (retrieved 2026-10-29). Values as compiled in the Lemonergy battery library, record cell/exide/classic-6-opzs-300-la: https://lemonergy.com/data/batteries/exide/classic-6-opzs-300-la/

The values are CC BY 4.0; the document and the passages quoted from it belong to its publisher. All sources of the library

Similar batteries

Nearest in the library by kind, format, chemistry, capacity and specific energy.

All Exide batteries · The battery library · Find and compare batteries